Calculate heating load: How many kW does your heat pump need?

Undersized means cold days with an expensive immersion heater, oversized means constant cycling and early wear. This calculator gives you the right scale — and shows which cylinders go with it.

In short: As a rule of thumb, a house in Austria needs around 15 W/m² of heating output (passive house) to 130 W/m² (unrenovated, before 1980) at a design outdoor temperature of −14 °C. A partly renovated house with 140 m² therefore comes to around 12,6 kW, a new build (2000–2015) of the same size to around 6,3 kW, plus around 0,2 kW per person for hot water. Reference values below, as of October 2026.

Everything at once? The heat pump calculator shows suitability, size, heating costs and federal state public subsidy in three steps.

140 m²
50 m²500 m²
2,5 m
2,2 m4,0 m — older building
4
110
Insulation standard
Climate zone
Heat distribution
Hot water

Your sizing

Design outdoor temperature −14 °C (climate zone Standard)

Total heating load
10,4 kW
Specific
90 W/m²
Buffer cylinder
200 l
Hot water cylinder
250 l
Annual heat demand21.000 kWh
Flow temperature on the coldest day45 °C
Expected seasonal performance factor3,5
Heat pump electricity consumption6.000 kWh/year

Find suitable appliances in this size

Quotes for this sizing

Rough estimate based on specific heating load. A room-by-room heating load calculation according to ÖNORM EN 12831 by the installer is binding.

Why bigger is not better: An oversized heat pump reaches its target temperature too quickly, switches off, cools down and starts again. This cycling wears out the compressor and lowers the seasonal performance factor. Modulating units cushion this, but they also have a lower modulation limit. If a quote includes significantly more kW than calculated here, ask for the heating load calculation it is based on.

Reference values: heating load by insulation standard and living area

Heating load of the building in kW at a design outdoor temperature of −14 °C (Austrian standard climate), 2,5 m room height, without hot water. These are the same rules of thumb the calculator above works with. As of: October 2026.

Insulation standardW/m²100 m²140 m²200 m²
Unrefurbished (before 1980)13013,0 kW18,2 kW26,0 kW
Partly refurbished (80s/90s)909,0 kW12,6 kW18,0 kW
Old building, fully refurbished606,0 kW8,4 kW12,0 kW
New build (2000–2015)454,5 kW6,3 kW9,0 kW
Efficient new build (from 2016)303,0 kW4,2 kW6,0 kW
Passive house151,5 kW2,1 kW3,0 kW

In mild locations (−12 °C) the heating load is around 6 % lower, in mountain areas (−20 °C) around 18 % higher. With your postcode, the calculator above uses the design outdoor temperature of your municipality according to OIB Guideline 6. Hot water adds around 0,2 kW per person, at least 0,8 kW.

Frequently asked questions

How many kW of heat pump do I need for 150 m²?

That depends mainly on the insulation standard. At a design outdoor temperature of −14 °C, a house with 150 m² of living space needs around 19,5 kW unrenovated, around 13,5 kW partly renovated, around 9,0 kW fully renovated and around 6,8 kW as a new build (2000–2015). Hot water adds around 0,2 kW per person, at least 0,8 kW. The calculator above uses your postcode and room height.

How do you calculate the heating load of a house?

Roughly: heated living area times the specific heating load in W/m². This depends on the insulation standard, from around 15 W/m² in a passive house to around 130 W/m² in an unrenovated older building (at −14 °C and 2,5 m room height). The building part is then converted to the design outdoor temperature of the location. Hot water adds around 0,2 kW per person. A room-by-room heating load calculation according to ÖNORM EN 12831 by the installer is binding.

Which design outdoor temperature applies to my house?

It is set for each municipality in OIB Guideline 6 (table of design outdoor temperatures, the basis of ÖNORM B 8110-5). If you enter your postcode above, the calculator uses the value for your municipality. Without a postcode it assumes the Austrian standard climate of −14 °C.

Isn't a bigger heat pump the safer choice?

No. An oversized heat pump reaches its target temperature too quickly, switches off and starts again. This cycling wears out the compressor and lowers the seasonal performance factor. Modulating units cushion this, but they also have a lower modulation limit. If a quote provides for significantly more kW than the heating load, ask for the calculation behind it.

How big do the buffer and hot water cylinders need to be?

As a rule of thumb, the calculator uses around 20 litres of buffer cylinder per kW of heating load, at least 100 litres (for defrosting and against frequent cycling), and around 60 litres of hot water cylinder per person, at least 200 litres. The exact size depends on the unit and the system.

Why does the data sheet show a different kW figure?

The value in the unit name or data sheet title usually refers to an outdoor temperature of +7 °C. What counts for sizing is the output at the design outdoor temperature of your location, and for an air source heat pump it is lower. Ask for the output at design outdoor temperature in the quote.

The sizing only becomes binding with a room-by-room heating load calculation by the installer. Request quotes from up to 3 checked installers.