Noise calculator: How loud is the heat pump at the neighbour's?
The most common point of dispute with air-source heat pumps — and one that can almost always be solved by choosing the right installation location. Important: The decisive factor is the level at the neighbouring property, not the number in the brochure.
Guideline value met
- Level at night at the neighbour's
- 36,2 dB(A)
- Guideline value at night
- 45 dB(A)
Reserve at night+8,8 dB
Level during the day41,2 dB(A)
Required minimum distance2,1 m
Notes
Free-field calculation without shielding by buildings and without air damping — i.e. the conservative approach. The assessment by the authority or experts according to ÖAL-Richtlinie Nr. 3 (Austrian noise protection guideline) is binding.
Site plan from above
The coloured circle is the area in which the night-time guideline value is exceeded. If the property boundary lies outside of it, you are on the safe side.
How it is calculated: The sound pressure level at the point of immission results from the sound power level of the device, the distance and the directivity caused by reflecting surfaces: Lp = LWA + 10·log₁₀(Q / 4πr²). Every doubling of the distance brings about 6 dB — twice as far away is therefore almost always more effective and cheaper than any noise protection measure. The guideline values come from ÖNORM S 5021 (Austrian standard); some federal states additionally link the public grant to noise limits, for example Vorarlberg to a maximum of 55 dB sound power. Details in the public grant check.