Noise calculator: How loud is the heat pump at the neighbour's?
The most common point of dispute with air-source heat pumps — and one that can almost always be solved by choosing the right installation location. Important: The decisive factor is the level at the neighbouring property, not the number in the brochure.
- Level at night at the neighbour's
- 36,2 dB(A)
- Guideline value at night
- 45 dB(A)
Notes
Free-field calculation without shielding from buildings and without atmospheric attenuation — i.e. the conservative scenario. The assessment by the authority or an expert witness in accordance with ÖAL-Richtlinie Nr. 3 Blatt 1 (noise guideline sheet 1) is binding.
Site plan from above
The coloured circle is the area in which the night-time guide value is exceeded. If the property boundary lies outside it, the location is probably uncritical according to this estimate. The rules of your federal state are what count.
What distance is enough? The table
Minimum distance to the property boundary or the neighbouring window so that the night-time guide value is complied with. Calculated without night-time reduction and without noise protection, i.e. the worst-case scenario. With silent mode (usually 3 to 8 dB quieter), significantly less is sufficient.
Residential area on the outskirts of town (40 dB at night)
| Sound power LWA | free-standing | on the house wall | in the corner |
|---|---|---|---|
| 50 dB(A) | 1,5 m | 2 m | 3 m |
| 55 dB(A) | 2,5 m | 3,5 m | 4,5 m |
| 60 dB(A) | 4 m | 6 m | 8 m |
| 65 dB(A) | 7,5 m | 10,5 m | 14,5 m |
Urban residential area (45 dB at night)
| Sound power LWA | free-standing | on the house wall | in the corner |
|---|---|---|---|
| 50 dB(A) | 1 m | 1,5 m | 1,5 m |
| 55 dB(A) | 1,5 m | 2 m | 3 m |
| 60 dB(A) | 2,5 m | 3,5 m | 4,5 m |
| 65 dB(A) | 4 m | 6 m | 8 m |
Sound power or sound pressure: the most common mistake
There are usually two numbers in the data sheet. The sound power LWA tells you how much noise the device emits, regardless of where it is located. The sound pressure Lp tells you what arrives at a specific point and decreases with distance: by around 6 dB for every doubling of distance. Brochures like to advertise the sound pressure at a distance of 1 m or 5 m, which sounds quieter. For planning, the sound power is what counts, and for the neighbour, the sound pressure at their property boundary. This is exactly what the calculator above calculates.
You can find the sound power in the device's data sheet. For subsidised devices, it is also listed in the GET-Produktdatenbank (GET product database).
Guideline values for each zoning category
How loud it is permitted to be at the neighbouring property depends on the zoning category; the assessment is conducted according to ÖAL-Richtlinie Nr. 3 Blatt 1. The key factor is the level at the neighbouring property. Stricter values apply at night, and because a heat pump also operates at night, the night-time value is usually the decisive factor.
| zoning (Widmung) | during the day | at night |
|---|---|---|
| quiet area / spa area (Ruhegebiet / Kurgebiet) | 45 dB | 35 dB |
| Residential area on the outskirts of town | 50 dB | 40 dB |
| Urban residential area | 55 dB | 45 dB |
| Core area (residential + commercial) (Kerngebiet) | 60 dB | 50 dB |
| commercial/industrial area (Betriebs-/Industriegebiet) | 65 dB | 55 dB |
These guideline values describe the total noise pollution in an area. For an individual heat pump at the property boundary, many federal states (such as Styria, Salzburg, Vienna) and OIB-Richtlinie 5 set values that are around 10 dB stricter, or 30 dB(A) at night in purely residential areas. When in doubt, plan with the stricter value and check with the building authority (Bauamt).
Proof of noise compliance (Schallnachweis) and building notification (Bauanzeige)
Whether you need a building notification (Bauanzeige) for an air-source heat pump and whether the authority requires proof of noise compliance (Schallnachweis) is regulated by the Bauordnung (building regulations) of your federal state. Especially if the distance to the property boundary is small, the building office can request an acoustic calculation. Ask at your Gemeindeamt (municipal office) before placing the order. The calculator here is a planning aid: it shows you early on whether an installation location is suitable. The proof itself is usually prepared by your installer or an expert.
How to make the heat pump quieter
- Distance: Doubling the distance reduces noise by around 6 dB, which is usually the cheapest lever.
- Avoid corners: In a building corner, two walls reflect the sound, which adds around 6 dB compared to a free-standing installation.
- Silent mode at night: Almost all current units have a night-time reduction of 3 to 8 dB.
- Choose a quiet unit: Differences of 10 dB in sound power level between units of the same capacity are normal.
- Acoustic insulation: An acoustic hood or a solid wall in the line of sight reduces noise by 5 to 10 dB, but a wall only works if it blocks the direct line of sight.
- Vibration isolation: Vibration dampers on the foundation prevent structure-borne noise from being transmitted into the house or to the neighbours.
Frequently asked questions
How loud is a heat pump allowed to be in Austria?
There is no nationwide uniform limit; Burgenland, for instance, links the simplified procedure in its building regulation to a maximum operating noise of 35 dB. Our calculator works with guideline values for each zoning category: 40 dB(A) at night in residential areas on the outskirts, 45 dB(A) in urban residential areas, in each case at the neighbouring property. For an individual heat pump at the property boundary, many federal states (such as Styria, Salzburg, Vienna) and OIB-Richtlinie 5 set values that are around 10 dB stricter, or 30 dB(A) at night in purely residential areas. The assessment by the building authority (Baubehörde) is binding.
What distance to the neighbour does an air-source heat pump need?
This depends on the sound power of the device, the installation setup and the zoning (Widmung). A device with 55 dB(A) on a house wall needs around 3,5 metres to the property boundary in a residential area on the outskirts of town without night-time reduction, while one with 65 dB(A) already needs around 10,5 metres. With silent mode, significantly less is sufficient. The table above shows typical values, the calculator shows your case.
What is the difference between sound power and sound pressure?
The sound power (L_WA) describes how much noise the device itself emits, regardless of the location. The sound pressure (L_p) is what arrives at a specific point and decreases with distance. Brochures often state the sound pressure at a distance of 1 m or 5 m; this is around 8 dB (1 m) to over 20 dB (5 m) below the sound power. For planning, you need the sound power from the data sheet.
Do I need a proof of noise compliance (Schallnachweis) for the heat pump?
This is regulated by the Bauordnung (building regulations) of your federal state, and the Baubehörde (building authority) can request an acoustic calculation for an air-source heat pump close to the property boundary. Ask at your Gemeindeamt (municipal office). This calculator is a planning aid, not an official proof; this is usually prepared by your installer or an expert.
Does the calculator apply to all federal states, including Tyrol or Vorarlberg?
As a planning aid, yes. It calculates with guideline values for each zoning category; some federal states set stricter values for heat pumps at the property boundary (see above). In addition, individual federal states link their public grant to noise limits, such as Vorarlberg to a maximum sound power level of 55 dB(A). The Grant Manager shows what applies in your federal state.
The right installation location is part of every good quote. Request quotes from a maximum of 3 checked installers.
What happens next?
- Which heat pump is suitable, and how loud is it for the neighbours?Model finder · suitable models for your house→
- Does a heat pump suit my house, and how much does it cost?Heat pump calculator · everything in three steps→
- Which grant do I get, and what do I need to do when?Grant manager · federal government, state and municipality→
- How efficient and quiet are the models?Model comparison · efficiency, noise, quality seal→