Installation location and distance to property boundary
There is no uniform minimum distance to the property boundary in Austria. State law, the device, the installation type and the sound level at the boundary all count.
- Device with 55 dB(A) sound power level on a house wall.
- The same device in a corner of a building: around 3 dB louder.
- Night-time guideline value in residential areas on the outskirts: 40 dB; for individual heat pumps, authorities often set values of 30–35 dB.
How close the outdoor unit of an air heat pump may be located to the property boundary is regulated by each federal state individually. There is no single distance limit in metres for the whole of Austria. Often it is not the distance that is capped, but the sound level reaching the boundary. The required distance is then determined by the device and the installation location.
Why this is important
The regulations vary widely:
- Salzburg: The simplified notification procedure is only open to an air heat pump if 40 dB(A) during the day and 33 dB(A) at night are maintained at the neighbouring property boundary. In purely residential areas, it is 30 dB(A) at night.
- Vorarlberg: Since June 2026, an air heat pump up to 30 kW can be exempt from permit requirements if minimum distances and other conditions are met. According to the Energy Institute (Energieinstitut), a unit with 52 dB sound power requires 5.9 m freestanding, or 9.6 m when mounted against a wall. Corner installation there always requires a permit.
- Lower Austria and Upper Austria: According to lärminfo.at, there are no centralised requirements for noise immissions.
Even if no permit is required, neighbours can, according to lärminfo.at, seek to prohibit noise that exceeds locally customary levels and significantly impairs the normal local use of their property.
What this means for you
- Ask your municipal office (Gemeindeamt) what applies to your property. They can also tell you whether townscape protection plays a role.
- Take the sound power level from the specification sheet and factor in the installation location.
- The quieter the unit, the closer it can usually be placed to the boundary.
The rules for each federal state can be found under Permits. You can estimate the sound level at the boundary using our sound calculator.