Design outdoor temperature
The design outdoor temperature is the cold rating used to calculate the heating load of your house. In Austria, it is fixed for each location.
- Heating load of the house: the colder it is outside, the more heat the house needs.
- Heat pump output: it drops slightly in cold weather.
- Bivalence point: this is where the lines intersect.
- To the left of this, a heating element or a second heat generator helps out.
The design outdoor temperature is a calculated value for particularly cold days at your location. The Federal Handbook for Energy Advisory Services (Handbuch für Energieberatung des Bundes) describes it as the daily mean outdoor temperature that is fallen below on average one day per year. So it is not the lowest value you will ever see on your thermometer.
Why this is important
The heating load of your house is calculated for precisely this temperature, which determines the required size of the heat pump. The lower the temperature, the more power the house needs. In Austria, according to the handbook, it lies between approximately -10 and -20 °C.
The basis used in the portal is the table of design outdoor temperatures for OIB Guideline 6 (OIB-Richtlinie 6). It specifies a value for the lowest point in each cadastral municipality (Katastralgemeinde). Two examples from the table:
- Bregenz: -10,0 °C
- Haugschlag (Bezirk Gmünd): -19,0 °C
The differences are therefore significant, even within a single federal state. A house on a slope is also often located higher than the lowest point of the cadastral municipality. According to the manual, town centres are on average 2 K warmer than open terrain.
What this means for you
- In the portal, you determine the value using your postcode: this identifies the municipality and its corresponding value from the table.
- This is an approximation. For the sizing, your installer should take into account the altitude of your building site.
- Ask in the quote about the output at your design outdoor temperature. For an air source heat pump, it is lower than at mild temperatures.
You can see the value for your location in the Heating load calculator. You can read why output in cold weather matters under Bivalence point.
Sources
- OIB: OIB-Richtlinie 6, Normaußentemperaturen (OIB-330.6-044/15, 16 June 2015) (accessed on 4 November 2026)
- BMVIT: Handbuch für Energieberatung (Berichte aus Energie- und Umweltforschung 13/2016) (retrieved on 4 November 2026)