Weather-compensated control system
The weather-compensated control system adjusts the flow temperature according to the outside temperature. To do this, it requires an outdoor sensor and a heating curve.
- Flat curve, typical for underfloor or wall heating: low flow temperature even in frosty conditions.
- Steep curve, typical for radiators: when it is cold, a significantly higher flow temperature is required.
- The flatter and lower the curve, the more efficiently the heat pump runs.
With weather-compensated control, a sensor measures the outdoor temperature. Using the heating curve, the control system derives how warm the heating water needs to be. If it gets colder outside, the flow temperature increases. Energieberatung NÖ (Energy Advisory Service Lower Austria) refers to this as outdoor-temperature-compensated control. Single- and two-family houses typically have this type of control, while flats tend to have room temperature control.
Why this is important
According to klimaaktiv, low flow temperatures have a positive effect on the seasonal performance factor and thus on electricity costs. In its brochure on efficient heat pumps, klimaaktiv therefore explicitly recommends weather-compensated temperature control.
However, the control system is only as good as its settings. According to Energieberatung NÖ (Energy Advisory Service of Lower Austria), the heating curve is too steep in up to 85 % of heating systems because it is set with a safety margin. In addition, the outdoor sensor doesn't know when the sun is shining in the living room. Thermostats exist for such external heat gains, see individual room control.
What this means for you
- When buying: According to the klimaaktiv Wegweiser (guide), the control system should have a daily and weekly programme, and in single-family houses also a holiday programme.
- At handover: Have someone show you where you can see the heating curve and how to change it.
- During operation: Proceed in small steps and write down the old setting.
- Reading the flow: It should be possible to read the flow and return temperatures for each heating group.
You can find out more under After installation.
Sources
- Energie- und Umweltagentur NÖ: Optimising the heating system (retrieved on 4 November 2026)
- klimaaktiv: So läuft Ihre Wärmepumpe rund. Tipps für die Planung und Installation (BMK, 2024) (accessed on 4 November 2026)
- klimaaktiv Guide to Good Heat Pump Installation (2026) (accessed on 4 November 2026)